Configuration parameters (CFG)
5.5 CFG4: Transponder parameters
RF290R
28
Configuration Manual, 09/2014, C79000-G8976-C377-01
Name
Description
When this parameter is saved on the reader, a plausibility test is run. If an error occurs, the reader replies with
STATUS = {0x11}.
Function
Description
LEVEL
Level of the RF output power, range: (1 ... 5 W)
•
b001 1 W
•
b010 2 W
•
b011 3 W
•
b100 4 W
•
b101 5 W
Notes:
•
The RF hardware is monitored constantly by a monitoring function. If an error occurs, the reader responds
to every command with the error code 0x84.
•
A change to "RF-POWER" only takes effect after configuration block CFG3 has been written to the
EEPROM and the reader has been reset.
5.5
CFG4: Transponder parameters
The parameters of the configuration block CFG4 contain general transponder settings.
Byte
0
1
2
3
4
5
6
Content
0x00
0x00
0x00
0x00
ISO15693
MODE
ISO15693
AFI1
ISO15693
OPTION
Default
-
-
-
-
0x0B
0x00
0x00
Byte
7
8
9
10
11
12
13
Content
0x00
ISO15693
AFI2
ISO15693
AFI3
ISO15693
AFI4
0x00
0x00
ISO-
Blockgröße
Default
-
0x00
0x00
0x00
-
-
0x04
Name
Description
ISO15693
-MODE
Bit
7
6
5
4
3
2
1
0
Function
0
0
AFI
NO-TS
DATA-
RATE
0
0
0
Function
Description
DATA-
RATE
•
b0 reserved
•
b1 high
NO-TS
•
b0 16 time slots
•
b1 1 time slot