SIMATIC RF166C
Operating Instructions, 12/2019, C79000-G8976-C578-01
49
Configuring
6
6.1
Assigning IP address via DHCP
Note that the IP address "192.168.0.254" has been assigned to the communication module
at the factory. If you want to configure the communication module using the WBM or address
it via OPC UA, it may be necessary to change the IP address.
Requirements
The Primary Setup Tool (V4.2 or higher) is installed and the communication module is
connected and running. You can find the Primary Setup Tool on the pages of "Siemens
Industry Online Support (
https://support.industry.siemens.com/cs/ww/en/view/19440762
)".
Procedure
Proceed as follows to assign a new, unique IP address and a unique device name to the
communication module:
1.
Open the Primary Setup Tool with "Start > All Programs > Siemens Automation >
SIMATIC > Primary Setup Tool".
2.
In the menu bar under "Settings > Set PG/PC interface..." select the network adapter
through which the communication module is connected to the PC and confirm with "OK".
3.
Click on the "Search" icon in the toolbar.
A dialog box opens with the information that a device was found in the network.
Содержание SIMATIC RF166C
Страница 6: ...Table of contents SIMATIC RF166C 6 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 14: ...Security recommendations SIMATIC RF166C 14 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 20: ...Description 3 3 Design SIMATIC RF166C 20 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 98: ...Programming via SIMATIC controller SIMATIC RF166C 98 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 156: ...Service and maintenance 10 5 Module replacement SIMATIC RF166C 156 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 160: ...Dimensional drawings SIMATIC RF166C 160 Operating Instructions 12 2019 C79000 G8976 C578 01 ...
Страница 176: ...Service Support SIMATIC RF166C 176 Operating Instructions 12 2019 C79000 G8976 C578 01 ...