8. Click on the "OS ..." object and then on "Edit" in the "Settings for Compiling/Downloading"
group.
The "Settings: Compile OS" dialog box is opened.
– On the "Which areas do you want to assign to which operator stations?" dialog page,
click "Next".
– On the "Select the network connections of the S7 programs belonging to the areas"
dialog page, click "Next".
– The first time you perform a compilation, on the "Select the data you want to compile
and the scope of the compilation" dialog page click "Entire OS" and select the "With
memory reset" check box in the "Scope" group.
– Click "Apply".
The project is analyzed and the "Settings: Download OS" dialog box opens.
– Enter the "Path to target OS computer" in the input line and click the option button "The
entire WinCC project" in the "Download" group.
9. Click "OK".
The "Settings: Download OS" dialog box closes.
10.Click "Start" in the "Compile and Download Objects" dialog box.
11.Click "OK" to close the next dialog boxes displayed.
12.Check and close the log file.
13.Click "Close".
The "Compile and Download Objects" dialog box closes.
Additional information
● Online help on the dialog boxes
7.5.12
How to set the CPU in RUN
Introduction
After you have downloaded the AS data and OS data to the CPU, you still have to set the CPU
to RUN mode.
Requirements
● The objects have been compiled and downloaded.
● The operator panel is open and in the foreground.
Procedure
1. Click "RUN" in the operator panel.
Commissioning and configuration of SIMATIC PCS 7 BOX RTX
7.5 Configuring SIMATIC PCS 7 BOX RTX in the PCS 7 network
BOX (V8.1)
Function Manual, 03/2015, A5E32711362-AC
85
Содержание SIMATIC PCS 7 BOX
Страница 6: ...Table of contents BOX V8 1 6 Function Manual 03 2015 A5E32711362 AC ...
Страница 8: ...Security information BOX V8 1 8 Function Manual 03 2015 A5E32711362 AC ...
Страница 14: ...Preface BOX V8 1 14 Function Manual 03 2015 A5E32711362 AC ...
Страница 24: ...WinAC RTX BOX V8 1 24 Function Manual 03 2015 A5E32711362 AC ...
Страница 26: ...Web Option for OS with SIMATIC PCS 7 BOX BOX V8 1 26 Function Manual 03 2015 A5E32711362 AC ...
Страница 126: ...Establishing the factory state BOX V8 1 126 Function Manual 03 2015 A5E32711362 AC ...