![Siemens SIMATIC PCS 7 BOX Скачать руководство пользователя страница 110](http://html.mh-extra.com/html/siemens/simatic-pcs-7-box/simatic-pcs-7-box_function-manual_376861110.webp)
4. If the dialog box warns you that the configuration data will be overwritten, make the decision
as follows:
– Click "OK" for initial commissioning.
– If the PC station is in process mode, you can only click "OK" during an allowed
interruption of the communication.
The "Stop Target Modules" dialog box opens.
5. Click "OK" in the "Stop Target Modules" dialog box to confirm.
The "Download" dialog box opens.
6. Click "OK" to start the download process.
The PC station is ready for operation once the configuration is loaded.
Switching the logs on the bus (Industrial Ethernet)
Note
Never disable the TCP/IP or ISO protocol during operation since they are both needed for the
configured operation!
If you want to change a bus in a system to a different protocol (from TCP/IP protocol to ISO
protocol, for example), temporarily set a mixed protocol (TCP/IP protocol and ISO protocol)
on the engineering station. Then, download the configuration data to all affected systems (for
example, the AS and engineering station).
9.12
How to Transfer the License Keys
Introduction
Use the Automation License Manager to transfer license keys for activating the installed
software package.
The license keys for SIMATIC PCS 7 AS mEC RTX are supplied on a license key USB stick.
The following license keys are part of the SIMATIC PCS 7 AS mEC RTX scope of delivery:
● WinAC; WinAC RTX
● SIMATIC PCS 7; RTX
● SIMATIC NET; SIMATIC NET BCE
Commissioning and configuring SIMATIC PCS 7 AS mEC RTX
9.12 How to Transfer the License Keys
BOX (V8.1)
110
Function Manual, 03/2015, A5E32711362-AC
Содержание SIMATIC PCS 7 BOX
Страница 6: ...Table of contents BOX V8 1 6 Function Manual 03 2015 A5E32711362 AC ...
Страница 8: ...Security information BOX V8 1 8 Function Manual 03 2015 A5E32711362 AC ...
Страница 14: ...Preface BOX V8 1 14 Function Manual 03 2015 A5E32711362 AC ...
Страница 24: ...WinAC RTX BOX V8 1 24 Function Manual 03 2015 A5E32711362 AC ...
Страница 26: ...Web Option for OS with SIMATIC PCS 7 BOX BOX V8 1 26 Function Manual 03 2015 A5E32711362 AC ...
Страница 126: ...Establishing the factory state BOX V8 1 126 Function Manual 03 2015 A5E32711362 AC ...