Installation and commissioning of the modems and routers
5.9 Installing and putting a SINAUT MD2, MD3, MD4 modem into operation
SINAUT ST7 station control system
System Manual, 09/2016, C79000-G8976-C178-10
233
Permitted ambient temperature
The SINAUT modems can be operated in the same temperature range specified for the S7-
300.
Table 5- 50 Permitted ambient temperature for SINAUT modems
Installation position
Permitted ambient temperature
Horizontal
0 to 60 °C
Vertical
0 to 40 °C
Dimensions for installing SINAUT modems
Table 5- 51 Dimensions for installing SINAUT modems
Module
Module width
Module height
Max. depth
Modem module
MD2, MD3 and MD4
80 mm
125 mm
120 mm or 180 mm
with open front panel
5.9.5
Connecting to the power supply
WARNING
Danger with the power turned on
Connecting the modem module when the power is on can damage the module. Therefore
connect the modem to the power supply only when the power supply is off.