Introduction to the SINAUT ST7 system
2.6 LTOP overvoltage protection modules
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
73
Figure 2-18 LTOP2 overvoltage protection module
The LTOP overvoltage protection module is available in two variants:
LTOP 1
Overvoltage protection module for use at the start or end of a 2-wire dedicated line.
LTOP2
Overvoltage protection module for use at the start or end of a 4-wire dedicated line or in a 2-
wire tapping point. In a 4-wire tapping point, two LTOP2 modules are required.
Table 2-3
Overview of the LTOP modules
Short name
Order no.
Explanation
LTOP1
6NH9821-0BC11
Single line transformer LTOP1, with one OPM
overvoltage protection module for use at the start or
end of a 2-wire dedicated line
LTOP2
6NH9821-0BC12
Double line Transformer LTOP2, with two OPM
overvoltage protection modules for use at the start or
end of a 4-wire dedicated line or a 2-wire tapping
point.
OPM
6NH9821-0BB00
OPM overvoltage protection module for LTOP1 and
LTOP2, plug-in (pack of 4)
The two LTOP variants have both screw terminals and an RJ-12 Western jack. The WAN
cable (RJ-12 - RJ-12) supplied with the MD2 and MD3 modems (used as dedicated line
modems) can be connected directly to this RJ-12 jack.
Note
The LTOP modules are not suitable for protecting dial-up connections (telephone and ISDN
network). Companies such as Phoenix and Dehn offer TAE6, S0, RJ-12, and RJ-45 jacks
with overvoltage protection.