Installing and putting a SINAUT modem into operation
6.7 ISDN dial-up modem MD4
SINAUT ST7 Station control system - System Manual
306
System Manual, 05/2007, C79000-G8976-C178-06
Table 6-46 Overview of the configurable standard profiles for dialing mode
Profile no. Description of the profile
Profile setting on DIL switch
SW1 (SW1.3 = ON)
0
AT command set
Data format:
•
In the command phase: Self-adapting
•
In the data phase: 10 bits (8N1)
(factory default)
2))
21
1
V.25bis,
1200 bps V.23 hx
Data format:
•
In the command phase: 10 bits (7E1)
•
In the data phase: 11 bits (8E1)
2))
21
2
V.25bis,
2400 bps V.22bis
Data format:
•
In the command phase: 10 bits (7E1)
•
In the data phase: 11 bits (8E1)
2))
21
3
V.25bis,
9600 bps V.32
Data format:
•
In the command phase: 10 bits (7E1)
•
In the data phase: 11 bits (8E1)
2))
21
Resetting the modem
If the configuration of the modem is unclear, you can reset to the factory default settings.
When you reset the modem, all four standard profiles for dialing mode are reset to the
factory defaults.
Procedure:
1. Power supply OFF
2. Set switch 3 to ON and switch 1, 2 and 4 to OFF
3. Power supply ON and then wait until the lower four LEDs have stopped flashing in
sequence.
4. Power supply OFF, set switch 3 to OFF
5. Select basic setting for dedicated line mode or standard profile for dialing mode and then
power ON
2))
21
Figure 6-50 Setting the DIL switch to reset the MD4 modem
Note
Following the reset, the settings made with the terminal program for the dedicated line
mode are deleted. The settings must therefore be transferred to the modem again using
the terminal program.