Product properties
3.11 SCALANCE X-100 button
SCALANCE X-100
Operating Instructions, 04, A2B00060666D
37
3.11
SCALANCE X-100 button
What does the button do?
Using the button, you can display and modify the set fault mask. The fault mask setting is
retained after device power off/on.
After pressing and holding down the button, the currently valid fault mask is displayed for
approximately 3 seconds. The LEDs of the monitored ports flash at a frequency of 5 Hz.
To change the fault mask, keep the button pressed. Within the next 3 seconds, the current
link status of the ports is displayed flashing at a frequency of 2.5 Hz. Keep the button
pressed. This new status is adopted as the new fault mask. The monitored ports now are
indicated by permanently lit LEDs until the button is released. As long as the LEDs are still
flashing, however, the saving of the mask can be stopped by releasing the button.
If an empty fault mask is set (no port is monitored), the two neighboring port LEDs flash on
and off alternately. To create an empty fault mask when you save as described above, the
port cables must not be connected.
At the same time, the monitoring of the connected power supplies is set with the fault mask.
The existence of the two power sources is monitored only if they are connected when the
fault mask is saved.
The failure of the link of one of the monitored ports or one of the monitored power supplies is
indicated by the red fault LED lighting up. At the same time, the signaling contact opens.
Note
Port monitoring and power supply monitoring are not activated when the device is delivered
(factory default).
Note
The PoE voltage at the PoE ports cannot be monitored using the fault mask.
Содержание SIMATIC NET SCALANCE X-100 Series
Страница 40: ...Product properties 3 12 Displays SCALANCE X 100 40 Operating Instructions 04 A2B00060666D ...
Страница 54: ...Approvals and markings SCALANCE X 100 54 Operating Instructions 04 A2B00060666D ...
Страница 60: ...Technical specifications 6 1 Technical specifications SCALANCE X 100 60 Operating Instructions 04 A2B00060666D ...
Страница 62: ...References SCALANCE X 100 62 Operating Instructions 04 A2B00060666D ...
Страница 68: ...Dimension drawings 8 1 Dimension Drawing SCALANCE X 100 68 Operating Instructions 04 A2B00060666D ...
Страница 72: ...Glossary SCALANCE X 100 72 Operating Instructions 04 A2B00060666D ...
Страница 74: ...Index SCALANCE X 100 74 Operating Instructions 04 A2B00060666D U UL approval 6 ...