Installation
3.1 Securing the housing
SCALANCE M826
30
Operating Instructions, 08/2018, C79000-G8976-C362-05
3.1
Securing the housing
Types of installation
For the device, you have the following options:
●
Wall mounting (no ceiling mounting)
●
Installation on a DIN rail
●
Installing on the S7-300 standard rail
●
Installing on the S7-1500 standard rail
●
Mounting on a pedestal
Strain relief for the cables
Regardless of the type of installation, make sure that there is suitable strain relief for the
connecting cable.
Shielding of cables
If cables are installed permanently, it is advisable to remove the insulation of the shielded
cable and to establish contact on the shield/PE conductor bar.
Permitted installation direction
●
Vertical installation (ventilation openings at the top and bottom)
Keep to the minimum clearances to other components or to walls of a housing so that the
convection ventilation of the device is not blocked.
●
Below at least 10 cm
●
Above at least 10 cm
Содержание SIMATIC NET SCALANCE M826
Страница 7: ...Preface SCALANCE M826 Operating Instructions 08 2018 C79000 G8976 C362 05 7 ...
Страница 8: ......
Страница 16: ...Security recommendations SCALANCE M826 16 Operating Instructions 08 2018 C79000 G8976 C362 05 ...
Страница 28: ......
Страница 37: ...Installation 3 6 Mounting on a pedestal SCALANCE M826 Operating Instructions 08 2018 C79000 G8976 C362 05 37 ...
Страница 38: ......
Страница 55: ...Connecting up 4 7 Replacing the PLUG SCALANCE M826 Operating Instructions 08 2018 C79000 G8976 C362 05 55 ...
Страница 56: ......
Страница 72: ...Approvals A 3 General approvals SCALANCE M826 72 Operating Instructions 08 2018 C79000 G8976 C362 05 ...
Страница 74: ...Index SCALANCE M826 74 Operating Instructions 08 2018 C79000 G8976 C362 05 ...