Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
± 4 kV @ 2.5
and 5 kHz
DC Power Ports
AC Power Ports
± 4 kV @ 2.5
and 5 kHz
IEC 61000-4-4
Burst (Fast
Transient)
Earth Ground Ports
± 4 kV @ 5 kHz
Signal Ports
± 4 kV Line-
to-Earth
± 2 kV Line-to-Line
4
DC Power Ports
± 2 kV Line-
to-Earth, ± 1
kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
± 4 kV Line-
to-Earth
± 2 kV Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced
(Conducted) RFI
Earth Ground Ports
10 V
3
100 A/m for 3 min
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 3 s
5
IEC 61000-4-10
Damped
Oscillating
Magnetic Field
Enclosure Ports
100 A/m for
1 s (100 kHz
and 1 MHz)
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
Signal Ports
DC Power Ports
IEC 61000-4-12
Damped
Oscillatory
AC Power Ports
2.5 kV Common
1 kV Differential
Mode @ 1 MHz
3
Signal Ports
DC Power Ports
IEC 61000-4-16
Mains Frequency
Voltage
AC Power Ports
30 V for 60 s
300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
Signal Ports
2.5 kV
Common Mode
1.0 kV
Differential Mode
DC Power Ports
IEC 61000-4-18
Damped
Oscillatory Wave
AC Power Ports
2.5 kV
Common Mode
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
40
RUGGEDCOM RSG2488F