Certification
6.2 EMC and Environmental Type Tests
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RSG2200F has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Note
• In the case of an all fiber port configuration, this product meets all Class 2
requirements. Otherwise, all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during
which disturbance errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during
which no disturbance errors will occur.
Test
Description
Test Levels
Severity Levels
Enclosure Contact
±8 kV
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
±4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
IEC 61000-4-4
Burst (Fast
Transient)
Earth Ground Ports
±4 kV
4
Signal Ports
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
4
DC Power Ports
±2 kV Line-to-
Ground, ±1 kV
Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced
(Conducted) RFI
Earth Ground Ports
10 V
3
40 A/m
Continuous
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
42
RUGGEDCOM RSG2200F
Installation Manual, 04/2022, C79000-G8976-1346-10