Access from and to the S7-200
A
Explanation of the symbols
The following tables summarize the access options from S7-300/400 to the S7-200 and from
the CP 234-1 to devices of the S7-200/300/400.
The symbols used in the tables have the following meaning:
Characte
r
Meaning
√
Is supported.
-
Is not generally supported.
X
Not possible if CPU with this firmware version is used.
RO
Read-only access (read only).
A.1
Access from S7-300/400 to S7-200
Supported access by S7-300/400 clients to S7-200 using STEP 7
S7-200 with CPU222, CPU224, CPU 226/XM
CPU firmware version
1.2
1.21
>1.21
Data types
BOOL
√
√
√
BYTE
√
√
√
CHAR
X
RO
√
WORD
√
√
√
INT
X
RO
√
DWORD
√
√
√
DINT
X
RO
√
REAL
X
RO
√
Memory areas
INPUT
√
√
√
OUTPUT
√
√
√
BIT MEMORY
√
√
√
DATA BLOCK
-
-
-
VARIABLES *
)
√
√
√