![Siemens SIMATIC NET CP 1243-1 DNP3 Скачать руководство пользователя страница 97](http://html.mh-extra.com/html/siemens/simatic-net-cp-1243-1-dnp3/simatic-net-cp-1243-1-dnp3_configuration-manual_1265365097.webp)
Configuration
3.19 Telecontrol connections
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
97
●
Conformity level
Relevant for all subscriber types
Specifies the DNP3 conformity level (DNP3 implementation level) supported by the
partner: Level 1, 2, 3, 4 and Level 4+
The conformity level referred to as Level 4+ contains the functional scope of Level 4 and
also the support of additional data types / variations; see also data point types in the
section Datapoint types (Page 109).
●
Temporary
The parameter is not supported.
Parameters for redundant connection paths
If redundant connection paths are configured, these are configured in the same way as the
main paths.
The parameters of the redundant connection paths are distinguished by the following suffix:
●
* (red)
The parameters of the redundant connection paths have the same functions as those for the
main path. See above for the meaning.
Examples:
●
Start interface (red.)
Interface of the starting point module through which the redundant connection runs.
●
End interface (red.)
Interface of the endpoint module through which the redundant connection runs.
3.19.5
Parameters of the DNP3 connections
3.19.5.1
General
If you select a connection in the "Telecontrol connections" table in the "Network data" editor,
additional parameter groups for this connection are displayed in the "Properties" tab of the
Inspector window.
In the parameter groups, you can check the connection, correct it if necessary and configure
additional properties.
Содержание SIMATIC NET CP 1243-1 DNP3