![Siemens SIMATIC NET CP 1243-1 DNP3 Скачать руководство пользователя страница 72](http://html.mh-extra.com/html/siemens/simatic-net-cp-1243-1-dnp3/simatic-net-cp-1243-1-dnp3_configuration-manual_1265365072.webp)
Configuration
3.14 E-mail configuration
Configuration - DNP3
72
Configuration Manual, 11/2018, C79000-G8976-C508-01
Configuring the synchronization via classic WAN networks
TIM modules (time master and slaves)
1.
In the parameter group "Receive time" of the TIM to be time master configure the time
source with one of the following options:
–
From NTP server
–
From local station
(take the time from the assigned CPU)
–
Receive time from WAN
(take the time from a network)
2.
Configure the interface of the master TIM as network node type "Master station".
3.
Configure the interfaces of the other TIM modules (time slaves) as network node type
"Node station" or "Station".
4.
If necessary, enable the "To local station" option in the "Send time" parameter group of
the stations if the assigned CPU should also be synchronized.
WAN network
1.
In the parameter group "Time-of-day synchronization" of the network enable the option
"Enable time-of-day synchronization for WAN".
2.
There configure the required synchronization cycle.
3.
Network the interfaces of all TIM modules involved with the WAN network.
The settings configured for the WAN network are adopted in the following parameter
groups of the connected TIM modules:
–
For the time master (Master station): "Send time" parameter group
–
For the time slaves (node stations / station) "Receive time" parameter group
3.14
E-mail configuration
Configuring e-mails in STEP 7
In the "E-mail configuration" entry, you configure the protocol to be used and the data for
access to the e-mail server.
In the message editor ("Messages" entry in STEP 7), you configure the individual e-mails,
see section Messages (Page 130).
E-mail configuration
If you want to use the secure transfer of e-mails, the module must have the current date and
the current time of day.
With the default setting of the SMTP port 25, the module transfers unencrypted e-mails.