Connecting
3.5 Connecting an external braking resistor
PDC1000(F)
Equipment Manual, 02/2020, A5E48775040-AA
27
Reference
Note the detailed information on the topic "Connecting" in the System Manual SIMATIC
MICRO-DRIVE Drive controller PDC
https://support.industry.siemens.com/cs/ww/en/view/109774126
3.5
Connecting an external braking resistor
Connecting an external braking resistor
WARNING
Damage to braking resistor - Risk of fire!
You must implement fire prevention measures for the external braking resistor (e.g. fire
protection housing, temperature fuse). The resistance of the externally connectable braking
resistor must be 3 ohms ± 10%.
The figure below shows the connection of an external braking resistor to interface X5051
(and X4060):
①
Basic insulation
4R+, 4R- Connection for external braking resistor
xL+ Supply voltage
R
External braking resistor
2DIx Digital input
Figure 3-5
Connection of external braking resistor (example)