Installing the S7-400
2-5
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Rules for Connection
When you connect a central rack to expansion racks, you must observe the
following rules:
•
You can connect up to 21 ERs of the S7-400 to one CR.
•
The ERs are assigned numbers to identify them. The rack number must be set
on the coding switch of the receive IM. Any rack number between 1 and 21 may
be assigned. Numbers must not be duplicated.
•
You may insert up to six send IMs in one CR. However, only two send IMs with
5 V transfer are allowed in one CR.
•
Each chain connected to the interface of a send IM can comprise up to four ERs
(without 5 V transfer) or one ER (with 5 V transfer).
•
The exchange of data via the communication bus is limited to 7 racks, meaning
the CR and ER numbers 1 to 6.
•
The maximum (total) cable lengths specified for the type of connection must not
be exceeded.
Type of Connection
Maximum (Total) Cable Length
Local connection with 5 V transfer via
IM 460-1 and IM 461-1
1.5 m
Local connection without 5 V transfer via
IM 460-0 and IM 461-0
5 m
Remote connection via IM 460-3 and
IM 461-3
102.25 m
Remote connection via IM 460-4 and
IM 461-4
605 m
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 20: ...Contents xx S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 66: ...Installing the S7 400 2 40 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 74: ...Addressing the S7 400 3 8 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 118: ......
Страница 170: ...Starting Up 6 20 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 194: ...Maintenance 7 24 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 252: ...Assembling the M7 400 8 58 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 310: ...Glossary Glossary 18 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 316: ...Index Index 6 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...