Addressing the M7-400 Modules
Which Modules Can Be Reached Via a Start Address?
Out of the M7-400 modules, only the application modules can be addressed
directly via an address.
The EXM 478 expansion module, ATM 478 AT adapter module and MSM 478
mass storage module cannot be accessed via the S7-400 backplane bus.
Communication between these modules and the CPU is exclusively via the
ISA bus.
Addressing Application Modules
In contrast to the signal modules which have a default address at least in the
central rack, the application modules have no default address.
This means that you must configure the addresses for the application modules in
STEP 7. The procedure can be found in the manual Configuring Hardware and
Communication Connections with STEP 7 V 5.1.
Addressing Interface Submodules
Addresses of interface submodules, which are operated in a module assembly with
an application module, are only visible locally for the corresponding application
module. The CPU can only address the interface submodules that are installed in
the same rack or an expansion rack belonging to the CPU and that can be reached
via the ISA bus. The addresses of these interface submodules must be configured
via STEP 7. There are no default addresses.
Local access of the CPU to interface submodules allocated to an application
module is not directly possible.
However, the interface submodules can be accessed indirectly via programmed
communication between CPU and application module (see also System Software
for M7-300 and M7-400, Program Design Programming Manual).
Addressing for Operation in the Segmented Rack
If you assemble M7 modules in a CR2 rack with a divided I/O bus (segmented
rack), the same applies to addressing of the application modules and interface
submodules as in a non-segmented rack.
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 20: ...Contents xx S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 66: ...Installing the S7 400 2 40 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 74: ...Addressing the S7 400 3 8 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 118: ......
Страница 170: ...Starting Up 6 20 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 194: ...Maintenance 7 24 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 252: ...Assembling the M7 400 8 58 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 310: ...Glossary Glossary 18 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...
Страница 316: ...Index Index 6 S7 400 and M7 400 Programmable Controllers Hardware and Installation A5E00069481 04 ...