SIMATIC IFP2200/2400 ITC2200/2400 frameless
30
A5E48015893-AC, 03/2021
Ambient conditions
Long-term storage
The following information applies to a device that is stored in its original packaging for longer than two weeks.
The device meets the requirements of IEC 60721-3-1:2018 Class 1K21.
Transport and short-term storage
Mechanical and climatic conditions for transportation and storage
The transport and storage conditions of this device meet the following requirements:
•
Mechanical ambient conditions according to IEC 60721-3-2:2018 class 2M4.
•
Climatic ambient conditions according to IEC 60721-3-2:2018 class 2K11
The following information applies to a device that is transported in the original packaging and weather-proof packaging and
stored for some time. The device has been tested according to these standards with the following additions and restrictions:
Type of condition
Permitted range
Free fall
≤
0.3 m
Temperature
–20 to +60 °C
Atmospheric pressure
1140 to 660 hPa, corresponds to an elevation of –1000 to 3500 m
Relative humidity
10% to 90%, without condensation
Pollutant concentration
SO2: < 0.5 ppm; relative humidity < 60%, no condensation
H
2
S: < 0.1 ppm; relative humidity < 60%, no condensation
Sinusoidal vibration in accordance with IEC 60068-2-6 5 to 8.4 Hz, deflection 3.5 mm 8.4 to 500 Hz, acceleration 1 g
Shock in accordance with IEC 60068-2-27
25 g, 6 ms, 1000 shocks
Note
If condensation has developed, wait until the device has dried completely before switching it on.
Do not expose it to direct heat radiation from a heating device.
Proper transport and storage, installation and assembly as well as careful operation and maintenance are prerequisites for
trouble-free and safe operation of the device.
Non-compliance will render the warranty for the device null and void.
Operating conditions
Mechanical and climatic conditions of use
The device is designed for use in locations protected from the effects of the weather. The conditions of use meet the
following requirements:
•
Mechanical ambient conditions according to DIN IEC 60721-3-3:2002 class 3M3
•
Climatic ambient conditions according to DIN IEC 60721-3-3:2019 class 3K3
Use with additional measures
The device should not be used at the following locations unless additional measures are taken:
•
In locations with a high degree of ionizing radiation
•
In locations with severe operating conditions, for example, due to:
–
Corrosive vapors, gases, oils or chemicals
–
Electrical or magnetic fields of high intensity
•
In systems that require special monitoring - for example:
–
Elevators
–
Systems in especially hazardous rooms