Parameterizing the Mobile Panel
5.7 General settings
TP1000F Mobile RO
90
Operating Instructions, 08/2017, A5E39831415-AA
The settings for the data and time of day have now been changed. The HMI device must be
restarted after changes in the following cases:
●
You have changed the time zone setting
●
You have changed the "Daylight savings time currently in effect" check box setting
See "Restarting the HMI device (Page 86)".
5.7.3
Entering and deleting a password
You can set and delete passwords with the following procedure:
●
For security mode, as described in the section "Using the HMI device in password-
protected security mode (Page 75)".
●
For security-related mode, as described in the section "Assigning a safety-related
operating mode (Page 115)".
Requirement
●
A password that does not contain the following characters:
–
Blank
–
The special characters ' or "
●
Password length ≤ 12 characters
NOTICE
Keeping the password
If the password is no longer available, you have no access to the Control Panel and the
Windows CE taskbar.
Backup password to protect it against loss.