Installing system components
3.5 Connecting the Mobile Panel
TP1000F Mobile RO
Operating Instructions, 08/2017, A5E39831415-AA
47
3.5.5
Replacing the connecting cable
Requirement
●
The connecting cable is unplugged from the connection box.
●
You have taken precautions to protect your device, see section "Connection information
(Page 43)".
●
Phillips screwdriver, size 2
Procedure
Open
1.
Place the HMI device on its front.
hhh
①
Screws for terminal compartment cover
②
Retainer
③
Screw for the retainer
④
Connecting cable
2.
Loosen the screw
③
.
3.
Loosen the screws
①
of the terminal compartment cover.
4.
Lift the terminal compartment cover to expose the connecting cable.
Replacing the connecting cable and closing the terminal compartment
1.
Remove the RJ45 plug from the X1 port.
2.
Remove the connector from the X80 port.
3.
Remove the connecting cable.
4.
Position the replacement cable so that the terminal compartment cover fits exactly over
the terminal compartment.
5.
Position the end of the connecting cable in the guide.