2-3
OP37/Pro Equipment Manual
Release 7/98
To install the unit, proceed as follows:
1. Make a mounting cutout in the front panel having a size of
436
-1.5
x 295
-1.5
(width x height in mm).
The front panel must not be thicker than 16 mm. You will find details of the
useful depth in the Technical Data contained in the appendix.
2. Insert the operator panel in the prepared cutout from the front. Take suit-
able precautions to prevent the OP from falling out of the front panel until
it has been properly secured.
3. Securely attach the OP to the front panel using the six screw clamps
1
supplied. Figure 2-1 shows the positions for the screw clamps.
1
1
1
1
1
1
Figure 2-1
Positions for the screw clamps
The screw clamps should be hooked into the OP casing and then the stud
screws tightened against the front panel from the back (see Figure 2-2).
Rear panel of OP
Stud screws
Allen key
Screw clamp
Figure 2-2
Locating and tightening the screw clamps
Installing in
control
cabinets/desks
Phaysical Installation