Planning use
3.2 Mounting the OP 73micro
OP 73micro, TP 177micro (WinCC flexible)
30
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
3.2
Mounting the OP 73micro
3.2.1
Mounting positions and fixation
Mounting position
The HMI device is designed for mounting in racks, switch cabinets, switchboards and
consoles. In the following, all of these mounting options are referred to by the general term
"cabinet."
The HMI device is self-ventilated and approved for vertical and inclined mounting in
stationary cabinets.
–
+
Figure 3-1
Approved deviations from the vertical mounting position of the OP 73micro without
auxiliary ventilation
Mounting position
Deviation from the vertical
①
Inclined
≤ –80°
②
Vertical
0°
③
Inclined
≤ 80°
CAUTION
Impermissible ambient temperatures
Do not operate the HMI device without auxiliary ventilation if the maximum permissible
ambient temperature is exceeded. The HMI device may otherwise get damaged and its
approvals and warranty will be void!