Technical information
8.4 Mechanical ambient conditions
Comfort Panels
190
Operating Instructions, 07/2017, A5E36770603-AB
Emission of radio interference
The following table shows the emitted interference from electromagnetic fields according to
EN 61000-6-4, measured at a distance of 10 m.
From 30 to 230 MHz
< 40 dB (
μ
V/m) quasi-peak
From 230 to 1000 MHz
< 47 dB (
μ
V/m) quasi-peak
See also
Notes about usage (Page 30)
8.4
Mechanical ambient conditions
8.4.1
Storage conditions
The following information is for a device that is transported and stored in its original
packaging.
The device meets the requirements according to IEC 60721-3-2 Class 2M2 with the following
amendments and limitations:
Type of condition
Permitted range
Free fall
≤
1 m
Vibration according to IEC 60068-2-6
5 .. 8.4 Hz, deflection 3.5 mm
8.4 ... 500 Hz, acceleration 1 g
Shock according to IEC 60068-2-27
250 m/s
2
, 6 ms, 1000 shocks
8.4.2
Operating Conditions
The following information applies to a device installed according to the specifications in these
operating instructions.
The device was tested based on IEC 60721-3-3 Class 3M3 with the following amendments
and limitations:
Type of condition
Permitted range
Vibration according to IEC 60068-2-6
5 ... 8.4 Hz, deflection 3.5 mm
8.4 ... 150 Hz, acceleration 1 g
Shock according to IEC 60068-2-27
150 m/s
2
, 11 ms, 3 shocks
Shock pulses within the specified range can be transferred to the display but do not impact
the functionality of the device.