Parameters/address space
4.3 Explanation of parameters
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
22
Manual, 08/2018, A5E41448857-AB
Parameters
Value range
Default
Parameter reas-
signment in RUN
Scope
Diagnostics: Wire break **
•
Disable
•
Enable
Enable
No
Channel
Smoothing
•
1
•
2
•
4
•
8
•
16
•
32
•
64
1
No
Channel
* See formula under Parameter assignment of discrepancy analysis for 1oo2 evaluation
(Page 27)
* Can only be set with 4 to 20 mA measuring range
4.3
Explanation of parameters
4.3.1
F-parameters
You must assign the PROFIsafe address (F-destination address together with F-source
address) to the F-module before you put it into operation.
●
You define the F-source address using the "Base for PROFIsafe addresses" parameter in
the F-CPU.
●
An F-destination address unique throughout the CPU is automatically assigned for each
F-module. You can manually change the F-destination addresses set in the hardware
configuration.
You can find information on F-parameters for the F-monitoring time, the PROFIsafe
addressing (F-source address, F-destination address) and the F-I/O DB in the manual
SIMATIC Safety - Configuring and Programming