Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
82
Manual, 06/2019, A5E46959434-AA
5.7.7
DALI_ECG_QUERY_GROUP
Description
DALI_ECG_QUERY_GROUP is used for querying the group membership of DALI control
gears.
●
When you set the input "PHY_DEV" to 1, this function block queries the group
membership from the physical device (refer to data flow path 6 (Page 23)).
●
When you set the input "PHY_DEV" to 0, this function block queries the parameters which
are saved in CM 1xDALI (refer to data flow path 2 (Page 23)).
You can set the group membership of control gear by using DALI_ECG_SET_GROUP
(Page 83).
Parameter
The following table shows the parameters of the function block:
Parameter Declaration Data type Memory
area
Description
QUERY
Input
BOOL
I, Q, M, D,
L or Con-
stant
Query the group membership of the control gear upon a rising edge.
ADDRES
S
USInt
I, Q, M, D,
L or Con-
stant
Specify the short address of the device.
Range: 0 to 63
PHY_DEV
BOOL
I, Q, M, D,
L or Con-
stant
Specify the location of parameters:
•
PHY_DEV = 0 : Query the parameters which are saved in CM
1xDALI.
•
PHY_DEV = 1 : Query the parameters from the physical device by
sending commands.
CM_DALI InOut
"DALI_CT
RL"
The data block of DALI_CTRL specifies the CM 1xDALI which com-
municates with the current function block.
BUSY
Output
BOOL
I, Q, M, D,
L
Status parameter:
•
BUSY = 0: Processing of job is terminated.
•
BUSY = 1: Job is still being committed.
ACTIVE
BOOL
I, Q, M, D,
L
Status parameter:
•
ACTIVE = 0: Job is not yet started.
•
ACTIVE = 1: Job is being executed.
DONE
BOOL
I, Q, M, D,
L
Status parameter:
•
DONE = 0: Job is not yet started or still executing.
•
DONE = 1: Job is executed without errors.
ERROR
BOOL
I, Q, M, D,
L
Status parameter:
•
ERROR = 0: No error occurs.
•
ERROR = 1: Error occurs during processing.