Analog Electronic Modules
12-54
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
12.8
2AI I 2WIRE Standard analog electronic module
(6ES7 134-4GB00-0AB0)
Order number
6ES7 134-4GB00-0AB0
Properties
•
2 inputs for current measuring
•
Input range:
4 to 20 mA, resolution 13 bits
Terminal assignment
The following table shows the terminal assignment of the 2AI I 2WIRE Standard for
the various terminal modules:
Table 12-39 Terminal assignment of the 2AI I 2WIRE Standard
View
Terminal assignment
Remarks
M
1--
M
0--
AUX1 (e.g. PE)
2
3
4
6
7
8
1
5
M
1+
M
0+
AUX1 (e.g. PE)
M
ana
M
ana
TM-E15S24-A1 and 2AI I Standard
CH1
CH0
mA
mA
AUX1 must be
assigned to PE.
A
A
Channel 0: Terminals 1 to A4
Channel 1: Terminals 5 to A8
M+: Input signal ”+”
M--: Input signal ”--”
M
ana
: Ground (from power
module)
The 2-wire transducers are
powered over the
measurement leads.
M
1--
M
0--
2
3
4
6
7
8
1
5
M
1+
M
0+
M
ana
M
ana
TM-E15S24-01 and 2AI I 2WIRE Standard
CH1
CH0
mA
n. c.
n. c.
Channel 0: Terminals 1 to 4
Channel 1: Terminals 5 to 8
M+: Input signal ”+”
M--: Input signal ”--”
M
ana
: Ground (from power
module)
The 2-wire transducers are
powered over the
measurement leads.
Terminals 4 and 8 can be
used for connection of cables
that are not required up to
30 VDC.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...