Analog Electronic Modules
12-26
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
12.2.3
Instructions and circuits for unused channels of the
analog input modules
•
”Disable” unused input channels in the configuration.
•
A disabled channel always return the value 7FFF
H
.
•
The cycle time of the modules is halved with the standard modules 2AI U, 2AI I
2WIRE, 2AI I 4WIRE, 2AI RTD Standard, 2AI RTD High Feature and 2AI TC
Standard, 2AI TC High Feature.
•
The cycle time remains unchanged with the 4AI I 2WIRE standard module.
•
The cycle time remains unchanged at 1 ms with the 2AI U, 2AI I 2WIRE and
2AI I 4WIRE high-speed modules.
•
To maintain the approved potential differences (U
CM
) bridges must be wired to
the terminal module on the unused channels. This is required for the following
modules:
Analog input module
TM connection terminal
Channel 0
Channel 1
1
2
3
4
5
6
7
8
2AI U Standard
2AI RTD Standard, 2AI RTD High
Feature,
2AI TC High Feature
2AI TC Standard
2AI U High Speed
12.3
Response of the Analog Modules during Operation and if
Faults Occur
This chapter describes:
•
The dependence of the analog input and output values on the supply voltage of
the electronic module and the operating states of the PLC.
•
The response of the analog electronic modules depending on the state of the
analog values in the specific value range.
•
The influence of errors on the analog inputs and outputs.
•
Use of the shield.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...