Analog Electronic Modules
12-5
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Note
The following applies with temperature measurements: The existing slope of the
characteristic line is retained in the over or under controller range when leaving the
linearized nominal range.
12.1.2
Analog value visualization for measurement ranges of the
analog input modules in SIMATIC S7 format
Introduction
The tables in this section contain the digitized analog values for the measuring
ranges of the analog input modules.
Since the binary representation of the analog values is always the same, these
tables contain only a comparison of the measuring ranges with the units.
Voltage measuring ranges:
80 mV,
2.5 V,
5 V,
10 V
Table 12-4 SIMATIC S7 Format: Measuring ranges
80 mV,
2.5 V,
5 V and
10 V
Measuring
Measuring
Measuring
5 V
Measuring
Units
range
80 mV
range
2.5 V
range
5 V
range
10 V
decimal
hexadeci-
mal
Area
> 94,071
> 2,9397
> 5,8794
> 11,7589
32767
7FFF
H
Overflow
94,071
2,9397
5,8794
11,7589
32511
7EFF
H
:
:
:
:
:
:
Overshoot
range
80,003
2,5001
5,0002
10,0004
27649
6C01
H
range
80,000
2,5
5,00
10,00
27648
6C00
H
60,000
1,86
3,75
7,50
20736
5100
H
:
:
:
:
:
:
Nominal
range
-- 60,000
-- 1,86
-- 3,75
-- 7,50
--20736
AF00
H
-- 80,000
-- 2,50
-- 5,00
-- 10,00
--27648
9400
H
-- 80,003
-- 2,5001
-- 5,0002
-- 10,0004
--27649
93FF
H
:
:
:
:
:
:
Undershoot
range
-- 94,074
-- 2,9397
-- 5,8796
-- 11,759
--32512
8100
H
range
< -- 94,074
< -- 2,9397
< -- 5,8796
< -- 11,759
--32768
8000
H
Underflow
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...