Power modules
10-3
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
10.2
PM-E 24 VDC power module (6ES7 138-4CA00-0AA0)
Order number
6ES7 138-4CA00-0AA0
Properties
•
The PM-E 24 VDC power module monitors the supply voltage for all electronics
modules which are part of the potential group. The supply voltage is supplied
via the TM-P terminal module
•
All electronic modules can be inserted in the potential group of the PM-E 24
VDC power module, except for 2DI AC120V ST, 2DI AC230V ST and
2DO 24--230 VAC/1 A.
!
Caution
Only apply the specified rated load voltage of 24 VDC to the TM-P terminal
module of the power module.
The rated load voltage applied must correspond to the power supply of the
electronic modules in the potential group.
•
The current status of the power module is saved in the process image of the
inputs (PII) via the status byte. The update is independent of enabling the ”No
load voltage” diagnosis (see Appendix C).
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...