Interface Modules
8-8
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
8.2
IM151-1 BASIC interface module (6ES7 151-1CA00-0AB0)
Order number
6ES7 151-1CA00-0AB0
Features
The IM151 1 BASIC interface module has the following features:
•
It connects the ET 200S with PROFIBUS DP via the RS485 interface.
•
It prepares the data for the electronic modules and motor starters that are fitted.
•
It supplies the backplane bus.
•
The PROFIBUS DP address of the ET 200S can be set by means of switches.
•
If the 24 VDC power supply is disconnected, the IM151-1 BASIC interface
module is also disconnected.
•
The maximum address space is 88 bytes for inputs and 88 bytes for outputs.
•
The reference potential M of the rated supply voltage of the IM151 1 BASIC to
the rail (protective conductor) is connected by means of an RC combination,
thus permitting an ungrounded configuration.
•
Operation as a DPV0 slave.
•
A maximum of 12 modules can be operated with the IM151 1 BASIC.
•
The maximum bus length is not relevant.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...