General Technical Specifications
7-8
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
7.3
Mechanical and climatic environmental conditions
Climatic environmental conditions
The following climatic environmental conditions apply:
Environmental conditions Operating ranges
Remarks
Temperature
from 0 to 60
_
C
For horizontal installation
from 0 to 40
_
C
For all other mounting positions
From 0 to 55
_
C
(see restrictions below)*
For vertical installation
Temperature change
10 K/h
Relative humidity
From 15 % to maximum 95 %
Without condensation
Air pressure
From 1080 hPa to 795 hPa
Corresponds to an altitude of
--1000 m to 2000 m
Contaminant concentration
SO
2
: < 0.5 ppm;
rel. humidity < 60 %, no dewing
H
2
S: < 0.1 ppm;
rel. humidity < 60 %, no dewing
Test:
10 ppm; 4 days
1 ppm; 4 days
* Restrictions for the operating range of 0 to 55
_
C in a vertical position
The operating range of 0 to 55
_
C in a vertical installation position is only permitted
for the following modules:
•
IM151-1 STANDARD: 6ES7 151-1AA02-0AB0
•
PM-E 24 VDC: 6ES7 138-4CA00-0AA0
•
2DI 24 VDC Standard: 6ES7 131-4BB00-0AA0
•
2DI 24 VDC High Feature: 6ES7 131-4BB00-0AB0
•
4DI 24 VDC Standard: 6ES7 131-4BD00-0AA0
•
4DI 24 VDC High Feature: 6ES7 131-4BD00-0AB0
•
2DO 24 VDC/0.5 A Standard: 6ES7 132-4BB00-0AA0
•
2DO 24 VDC/0.5 A High Feature: 6ES7 132-4BB00-0AB0
•
4DO 24 VDC/0.5 A High Feature: 6ES7 132-4BD00-0AA0
•
2DO 24 VDC/2 A Standard: 6ES7 132-4BB30-0AA0
•
2DO 24 VDC/2 A High Feature: 6ES7 132-4BB30-0AB0
•
4DO 24 VDC/2 A Standard: 6ES7 132-4BD30-0AA0
•
2RO NO 24-120 VDC/5 A 24-230 VAC/5 A: 6ES7 132-4HB00-0AB0
Note
All of the supply and load voltages of the ET 200S must not exceed 24 VDC. This
voltage limit must be enforced.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...