General Technical Specifications
7-7
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Sine-shaped interference
The following table shows the electromagnetic compatibility of the ET 200S
distributed I/O system when confronted with sinusoidal interference.
RF irradiation to IEC 61000-4-3
electromagnetic RF field
RF coupling to
IEC 61000-4-6
Amplitude-modulated
Pulse-modulated
80 to 1000 MHz
900 MHz
5 MHz
0.15 to 80 MHz
10 V/m
10 V
eff
unmodulated
80% AM (1 kHz)
50% ED
80% AM (1 kHz)
200 Hz repetition frequency
150
Ω
source impedance
Emission of radio interference
Emission of electromagnetic fields to EN 55011: Limit class A, group 1 (measured
at a distance of 10 m.)
Frequency
Emitted interference
From 30 MHz to 230 MHz
< 40dB (
m
V/m)Q
From 230 MHz to 1000 MHz
< 47dB (
m
V/m)Q
Shipping and storage conditions
The ET 200S distributed I/O system exceeds the requirements of IEC 61131-2 as
regards shipping and storage conditions. The following specifications apply to
modules shipped or stored in their original packaging.
Type of condition
Permitted range
Free fall
≤
1 m
Temperature
from --40
_
C to + 70
_
C
Temperature change
20 K/h
Air pressure
From 1080 hPa to 660 hPa (corresponds to
an altitude of --1000 m to 3500 m)
Relative humidity
From 5 % to 95 %, without condensation
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...