Commissioning and Diagnostics
6-40
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Power module error types
The diagnostic message is reported on channel 0 and applies to the whole module.
Table 6-12 Power module error types
Power modules electronic
modules
Error type
Meaning
Remedy
PM-E 24--48
VDC/
120--230 VAC
PM-E 24
VDC
PM-E
24--48 VDC
17
D
10001: Encoder or
load voltage missing
No supply voltage,
or inadequate
supply voltage.
Correct the process
wiring. Check the
supply voltage.
------
18
D
10010: Fuse defect
The fuse in the
power module has
tripped.
Replace the fuse.
Digital electronic module error types
Table 6-13 Digital electronic module error types
Digital electronic
modules
Error type
Meaning
Remedy
2DI 24 VDC High
Feature
1
D
00001: Short-circuit
Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
Correct the process
wiring (sensor
wiring).
4DI 24 VDC High
Feature
1
D
00001: Short-circuit
(in connection with
IM151-1 BASIC /
IM151-1 STANDARD,
as of
6ES7 151-1AA02 0AB0,
IM151-1 FO
STANDARD, as of
6ES7 151-1AB01-0AB0)
or IM151-1 HIGH
FEATURE
Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
Correct the process
wiring (sensor
wiring).
26
D
11010: External
error/fault
(in connection with
IM151-1 STANDARD, to
6ES7 151-1AA01-0AB0
or IM151-1 FO
STANDARD, to
6ES7 151-1AB00-0AB0)
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...