Commissioning and Diagnostics
6-36
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
6.1.6.7
Module information
Definition
The module status indicates the status of the configured modules and expands on
the module diagnosis as regards the configuration. The module status begins after
the module diagnosis and comprises:
•
7 bytes in the case of the IM151-1 BASIC
•
20 bytes in the case of the IM151-1 STANDARD, IM151-1 FO STANDARD and
IM151-1 HIGH FEATURE.
Module status
The module status for the ET 200S with the IM151-1 BASIC is structured as
follows:
Byte 9
Byte 10
7
0
Byte 11
7
0
82
H
0
H
0
H
7 6 5 4
1
3 2
0
Byte 13
Byte 12
Bit no.
Modules 1 to 4
Byte 14
Modules 5 to 8
Byte 15
Modules 9 to 12
00
B
: module OK; valid user data
01
B
: module error; invalid user data
10
B
: incorrect module; invalid user data
11
B
: no module (or module failure);
invalid user data
Status type: Module Status
irrelevant
irrelevant
7
0 Bit no.
Code for module status
0 0
5
6
Length of the module status
including byte 15 (= 7 bytes)
1 1
1
0
0
0
1
2
3
4
Figure 6-23
Structure of the module status for the ET 200S with the IM151-1 BASIC
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...