Wiring and Fitting
5-22
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Installing simplex connector
Note
The fiber-optic duplex line cable have the following maximum lengths:
•
PROFIBUS Plastic Fiber Optic Standard Cable
50 m
•
PROFIBUS PCF Fiber Optic Standard Cable
300 m
1. Remove about 30 cm of the cladding of the fiber-optic duplex cable.
2. Attach the Simplex plugs to the fiber-optic duplex cable.
For detailed assembly instructions for the Simplex plugs see the
”SIMATIC NET
PROFIBUS Networks”
manual
Tip:
Do not simply attach the two Simplex plugs together, but connect them to
form a duplex plug. In this manner you will achieve a better hold in the
connector adapter.
IMPORTANT:
The cut and polished surface of the plastic fiber must be
absolutely smooth and flat. The plastic cladding also must not stick out or be
separated roughly. Each deviation causes strong attenuation of the light signal
over the fiber-optic cable.
3. Put the simplex connector in the plug-in adapter for the IM151-1 FO
STANDARD and the fiber-optic cable in the appropriate cable ducts. Snap the
connector adapter closed so that you can hear clearly that the side units have
made contact with each other.
When inserting the plugs into the plug adaptor make sure that they are in the
correct position: sender always up and receiver always down.
Connector
adapter for the
IM151-1 FO
STANDARD
Snap the two simplex connectors
together such that you get a ”duplex
connector.”
Fiber optic duplex
line
Maximum 30 mm bending radius
Tip:
Cut the lower cable about 10 mm shorter
than the upper cable so that you achieve
better arrangement for the wires.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...