Setting the PROFIBUS address
Features
The PROFIBUS address defines the address at which the ET 200S distributed I/O
system is found on the PROFIBUS DP.
Prerequisites
•
The PROFIBUS DP address for the ET 200S is set on the IM151-1 interface
module by means of DIP switches. The DIPswitches are on the front of the
interface module, protected by a sliding window.
•
The permitted PROFIBUS DP addresses are 1 to 125.
•
Each address can be assigned only once on the PROFIBUS DP.
Tool required
3 mm screwdriver
Setting the PROFIBUS DP address
1. Slide the window on the interface module upward.
2. Use a screwdriver on the DIP switches to set the desired PROFIBUS DP
address.
3. Close the window.
64
32
16
8
4
2
1
ON
Interface module
OFF
Example:
DP address =
64
+ 32
+ 2
+ 1
= 99
_______
ET 200S
*
*
Only with IM151-1 STANDARD, IM151-1 FO STANDARD:
Reserved for future upgrades. This switch must be in the
OFF
position.
Figure 4-9
Setting the PROFIBUS Address
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...