Wiring
6.8 Front connector for the I/O modules
ET 200MP Distributed I/O System
66
System Manual, 01/2013, A5E03723484-01
Use of the potential bridges for I/O modules without shield contact element
With the delivered potential bridges, for digital modules with a maximum rated voltage of 24
V DC, you can bridge the terminals for the voltage supply and thus reduce the wiring effort.
The bridges can be inserted between the facing terminals 9 and 29, 10 and 30, 19 and 39,
and 20 and 40.
Reference
Further information on wiring the inputs and outputs can be found in the Product Manuals for
the I/O modules.
6.8.3
Wiring front connectors for I/O modules with shield contact element
Introduction
The front connector connects the I/O modules with the process signals.
Requirements
●
The I/O modules are installed on the mounting rail.
●
Wire the front connectors with the supply voltage turned off.
●
Follow the wiring rules (Page 57).
●
Prepare the lines, depending on the method of wiring.
Tools required
●
Stripping tool
●
3 to 3.5 mm screwdriver
Содержание simatic ET 200MP
Страница 4: ...Preface ET 200MP Distributed I O System 4 System Manual 01 2013 A5E03723484 01 ...
Страница 8: ...Table of contents ET 200MP Distributed I O System 8 System Manual 01 2013 A5E03723484 01 ...
Страница 22: ...Product overview 2 4 Properties ET 200MP Distributed I O System 22 System Manual 01 2013 A5E03723484 01 ...
Страница 76: ...Wiring 6 9 Marking the I O modules ET 200MP Distributed I O System 76 System Manual 01 2013 A5E03723484 01 ...
Страница 118: ...Service Support ET 200MP Distributed I O System 118 System Manual 01 2013 A5E03723484 01 ...
Страница 126: ...Index ET 200MP Distributed I O System 126 System Manual 01 2013 A5E03723484 01 ...