Type of output
With this parameter, you set the output type, for example, voltage. For any unused channels,
select the
disabled
setting. For a disabled channel, the conversion time and integration time
of the channel = 0 s, and the cycle time is optimized.
Output range
With this parameter, you set the output range of the selected output type.
Diagnostics, wire break (in current mode)
When this parameter is enabled, the
Wire break
diagnostics event is generated when a wire
break is detected. This diagnostics event cannot be detected in the zero range.
Diagnostics, short circuit (in voltage mode)
If you enable this parameter, a diagnostics event is generated in the event of a short circuit in
the output line. This diagnostics event cannot be detected in the zero range.
Diagnostics, overload
If you enable this parameter, the diagnostics event is generated in the event of an overload.
Substitute values
With this parameter, you enter a substitute value that the module is to output in CPU-STOP
mode. The substitute value must be in the nominal range, overrange, or underrange.
10.2.4
Output ranges of analog output device
Output ranges for voltage and current: ±10 V; ±20 mA
Units
Output range
±10 V
Output range
±20 mA
Decimal
Hexadecimal
Range
0.00 V
0.00 mA
32767
7FFF
H
32512
7F00
H
Overflow
11.76 V
23.52 mA
32511
7EFF
H
27649
6C01
H
Overrange
196
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device analog input/analog output
10.2 I/O device analog output