3-8
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
3.4
Digital Input/Output Module ET 200C; DI 16/DO 16
DC 24V
(6ES 143-0BL00-0XB0 and 6ES7 143-0BL10-0XB0)
The digital input/output module ET 200C; DI 16/DO 16
DC 24V has the
following characteristics:
Degree of protection IP 66/IP 67 (see Installation rules, Section 4.1)
Two versions of the module are available with different connection
systems for the input/output channels:
with circular connectors
³
6ES7 143-0BL00-0XB0
with cable gland and conduit thread
³
6ES7 143-0BL10-0XB0
Output current per channel: 2 A
Choice of nine different baud rates:
9.6, 19.2; 93.75; 187.5; 500; 1500; 3000; 6000 and 12000 kbaud
The baud rates 3000, 6000 and 12000 kbaud can only be used if the
module is operated with the IM 308-C (see Section 1.2).
Diagnostics for 4 outputs of a channel group for wire break,
short-circuit/overload and load voltage of the outputs (LED ”DIA” for
output x.0 to x.3, LED ”DIA” for output x.4 to x.7; x = 0.1).
Diagnostics for 4 inputs of a channel group for wire break,
short-circuit/overload of the sensor supply (LED ”DIA” for input x.0 to
x.3, LED ”DIA” for input x.4 to x.7; x = 0.1).
The diagnostics can be output via the IM 308-B master interface module.
Diagnostics can be switched off with COM ET 200 by means of the
parameterization telegram (see Section 5.1.2).
LEDs for
–
RUN
–
BF (bus fault)
–
DIA (group diagnostics for 4 inputs and 4 outputs)
–
Load voltage monitoring (U
L1
, U
L2
)
–
Status of the inputs/outputs
Attachment of the module without opening the cover (drill-hole template
at the back of the manual)
Replaceable labelling strips (order no. 6ES7 790-2CA11, 5 labelling strips
on one DIN A4 sheet)
Characteristics
ET 200C Components
Содержание SIMATIC ET 200C
Страница 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Страница 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Страница 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Страница 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Страница 122: ...4 54 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Mechanical and Electrical Installation ...
Страница 136: ...5 14 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Address Assignment and Parameterization with COM ET 200 ...
Страница 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Страница 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Страница 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Страница 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Страница 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Страница 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Страница 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...