Diagnostics and maintenance
4.8 Diagnostics in the user program
PROFINET with STEP 7
Function Manual, 05/2021, A5E03444486-AL
97
4.8
Diagnostics in the user program
4.8.1
Diagnostics and configuration data records
Diagnostics mechanism
The IO device outputs a diagnostics interrupt to the IO controller when it detects faults such
as wire break on an IO module. This interrupt calls a corresponding organization block in the
user program (diagnostics interrupt OB82), in order to generate a defined (programmed)
response to the fault and passes a diagnostics data record.
Diagnostics data records in PROFINET IO
There are two different types of diagnostics data record:
1.
Channel diagnostics data records
Channel diagnostics data records are generated if a channel is in an error state and / or has
triggered an interrupt.
A diagnostics data record of length 0 is returned if there is no fault.
2.
Vendor-specific diagnostics data records
The structure and size of vendor-specific diagnostics data records depend on the vendor's
settings.
For information about vendor-specific diagnostics data records, refer to the appropriate
device manual.
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......