Technical specifications
10.2 Electromagnetic compatibility
Distributed I/O system
System Manual, 08/2021, A5E31861578-AJ
105
Sinusoidal disturbance variables
The following tables show the electromagnetic compatibility of the distributed I/O systems to
sinusoidal disturbance variables.
Table 10- 4 RF radiation
RF radiation according to IEC 61000-4-3
Electromagnetic RF field, amplitude modulated
Corresponds to degree of severity
80 MHz to 1000 MHz
10 V/m
3
1.4 GHz to 6 GHz
3 V/m
2
80% AM (1 kHz)
Table 10- 5 RF coupling (signal and supply cables)
RF coupling according to IEC 61000-4-6.
Corresponds to degree of severity
0.15 MHz to 80 MHz
3
10 V
rms
unmodulated
80% AM (1 kHz)
150
Ω
source impedance
Emission of radio frequency interference
The following table shows the interference emission of electromagnetic fields according to
55016: limit class A, group 1.
Table 10- 6 Interference emission of electromagnetic fields
Frequency
Interference emission
Measuring distance
30 MHz to 230 MHz
<40 dB (µV/m) Q
10 m
230 MHz to 1000 MHz
<47 dB (µV/m) Q
10 m
1 GHz to 3 GHz
<76 dB (µV/m) P
3 m
3 GHz to 6 GHz
<80 dB (µV/m) P
3 m
24 V supply connection
The following table shows measurement ranges for low voltage according to EN 55016.
Table 10- 7 Interference emission from the power supply
Frequency
Interference emission
0.15 MHz to 0.5 MHz
79 dB (µV) Q
66 dB (µV) M
0.5 MHz to 30 MHz
73 dB (µV) Q
60 dB (µV) M
Содержание SIMATIC ET 200AL
Страница 2: ......
Страница 143: ......
Страница 218: ......
Страница 250: ......
Страница 296: ......
Страница 337: ......
Страница 365: ......
Страница 392: ......
Страница 419: ......
Страница 451: ......
Страница 483: ......
Страница 597: ......
Страница 648: ......
Страница 702: ......
Страница 739: ......
Страница 781: ......
Страница 804: ......
Страница 828: ......
Страница 853: ......
Страница 880: ......
Страница 906: ......
Страница 996: ...Diagnostics ...
Страница 1121: ......
Страница 1565: ......