C-12
Communications Processor CP 541
EWA 4NEB 812 6188-02
C.6
Default DB1
When delivered and after a reset, the CP 541 contains a default DB1. The
settings of the default DB1 in the CP 541 are such that you can use it im-
mediately in most cases. You need only adjust the station number.
The following list contains an explanation of the default DB1.
Indication
Explanation
KS =’DB1
’;
KS =’SL2:
’;
KS =’TLN 1
’;
KS =’STA AKT
’;
KS =’BDR 500
’;
KS =’HSA 30
’;
KS =’TRT 30000 ’;
KS =’SET 80
’;
KS =’ST 1000
’;
KS =’SDT 1 80
’;
KS =’SDT 2 360 ;
’;
Block ID SL2
Station number 1
Station status active
Transmission rate: 500 Kbps
Highest station number of all L2 masters: 30
Token rotation time: 30000 bit times = 60 ms
Setup time: 80 bit times = 0.16 ms
Slot time: 1000 bit times = 2 ms
Shortest station delay time:
80 bit times = 0.16 ms
Greatest station delay time:
360 bit times = 0.72 ms
KS =’#COM:
’;
KS =’L1M 0
’;
KS =’BSAP 52
’;
KS =’POL 10
’;
KS =’UPDL 10
’;
KS =’PRI ........ ;#
’;
Block identifier: COM (remarks)
Address conversion to station number: 0
Broadcast service access point: 52
L1 send delay time: 100 ms
Priority: ...; a dummy character has been
entered.
KS =’#DPS:
’;
KS =’NWI 16
’;
KS =’NWO 16
’;
KS =’DPWD 50 ;#
’;
Block identifier: DPS (remarks)
Length of input data: 16 words
Length of output data: 16 words
DP watchdog: 500 ms
KS =’END
’;
The two blocks COM and DPS are marked as remarks. If you wish to use
these two blocks, you must overwrite the “#” remark marks with a blank.
Note
If you remove the comment characters from block COM, you must either
clear parameter PRI or define you own priority list.
The CP 541 cannot run with the dummy character for the values of PRI in
default DB1.
Introduction
Default DB1
Important
Parameters of DB1