Diagnostics with the CP 440
8-5
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
8.3
Diagnostic Messages of the Function Blocks
Every function block has a STATUS parameter for error diagnostics. The STATUS
message numbers always have the same meaning, irrespective of which function
block is used.
Number system Event Class/Event Number
The figure below illustrates the structure of the STATUS parameter.
ST
A
TUS
Bit no. 15
13 12
8
7
0
Reserve
Event class
Event number
(Error number)
Figure 8-1
Structure of the STATUS Parameter
Example
The figure below illustrates the contents of the STATUS parameter for the even
when a job is aborted due to a cold restart, warm restart or reset (event class:
1EH, event number: 0DH).
ST
A
TUS
2
4
2
0
2
7
2
0
Reserve
Event
class: 1EH
Event number
(error number): 0DH
x
x
x
1
1
1
1
0
0
0
0
0
1
1
0
1
In the event of a job being aborted due to a cold restart, warm restart or reset
Figure 8-2
Example: Structure of the STATUS parameter in the event of a job being
aborted due to a cold restart, warm restart or reset