
Requirement
● The new field device (without necessary hardware addressing) has been reset to the factory
state.
You can find information about this in section "Restoring the state of delivery (Page 125)".
● The field device is not connected to the service port of the CFU PA.
● The field device is connected to a port of the CFU PA that has not yet been configured in the
CFU PA.
● The spur line to the field device is enabled.
Basic procedure
Observe the following:
● If the spur line to the field device is not active, the power supply is deactivated via the
fieldbus.
The field device is not recognized.
● The user must configure the correct field device and download the configuration to the CFU
PA in SIMATIC PDM.
When the configuration is downloaded, the connection to the field device can be enabled.
Once the new field device has been connected (and the spur line to the field device has been
activated again using SIMATIC PDM), the CFU PA can communicate with the field device.
10.11
CFU PA: Re-reading field device data or restarting the field device
The commissioning wizard "CFU ... Configuration" integrated into SIMATIC PDM offers the
relevant expert functions for the individual fieldbus connection (FIELDBUS; FB<n>).
The power supply to the fieldbus connection (FIELDBUS; FB<n>) is briefly switched off and on
again.
Procedure
1. Double-click the CFU PA in HW Config.
SIMATIC PDM opens
2. Open the commissioning wizard.
3. Click the "Expert functions".
4. Click the relevant button.
NOTICE
The field device is disconnected from the process mode
The warning at resetting has to be confirmed since the field device is disconnected from
process operation at a reset (fails).
Then the commissioning phase of the field device starts again.
Servicing and maintenance
10.11 CFU PA: Re-reading field device data or restarting the field device
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
123
Содержание Simatic CFU
Страница 8: ...Table of contents SIMATIC CFU 8 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 10: ...Security information SIMATIC CFU 10 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 16: ...What is a Compact Field Unit SIMATIC CFU 16 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 34: ...Operation planning 4 9 Use in hazardous areas SIMATIC CFU 34 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 46: ...Operating modes and functions 5 4 Measure frequency SIMATIC CFU 46 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 54: ...Installation 6 4 Removing the CFU SIMATIC CFU 54 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 202: ...Appendix A 10 Contact SIMATIC CFU 202 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 216: ...Glossary SIMATIC CFU 216 Commissioning Manual 08 2019 A5E39252870 AD ...
Страница 220: ...Index SIMATIC CFU 220 Commissioning Manual 08 2019 A5E39252870 AD ...