Procedure
1. Open the control recipe in the BCC.
2. Right-click on the recipe step with the ESIG symbol and open the "Sign" shortcut menu.
3. Enter the required electronic signature and a comment.
4. Close the dialog with "OK".
Result
After signing with a forced comment entry, the held step is resumed.
9.8
Batch control
9.8.1
Requirements for batch processing
Requirements
Batch control with SIMATIC BATCH requires the PCS 7 OS (WinCC) system. Before a batch
can be processed, the following requirements must be met:
● The PCS 7 OS system must be operating in runtime mode (online).
● The SFC type instances or BATCH interface blocks must be known to the PCS 7 OS data
manager.
● The bus connection between the PCS 7 operator stations (OS) and the automation systems
(AS) must be active.
● The batches for the control recipes must have been generated already; in other words, the
batches have the "Released" status.
● The operator has the necessary permissions for batch control in the user management of
SIMATIC BATCH.
BATCH Control Center
9.8 Batch control
SIMATIC BATCH V8.2
380
Operating Manual, 02/2016, A5E35958174-AA
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...