3. Confirm with "OK".
Result: The information for the signature is displayed in the "Signatures" table.
– If several signatures are required and the "All" option is active, all the signatures must
be entered at the same time in one open "SIMATIC Logon Service - Signature" dialog
box before clicking "OK".
– If several signatures are required and the "Individually" option is active, the open
"SIMATIC Logon Service - Signature" dialog box can be closed again with "OK" after
entering a signature.
In both cases, the signature is complete, only when all signatures have been entered.
4. Confirm the "SIMATIC Logon Service - Signature" dialog box with "OK".
Note
Remember that it may be necessary to complete the signatures within a specified time. The
time available and the expiration of the time is displayed in the "Times" group in the
"SIMATIC Logon Service - Signature" dialog box.
9.7.3
Forcing comment entry
Comment field in the "Sign" dialog
To sign operator actions, or the editing of recipes, you can now also force entry of a comment.
This means that the operator or the person who is required to sign electronically per user role,
is forced to enter a comment in the comment field of the "Sign" dialog, in addition to signing
electronically. Only then can he close the dialog with the "OK" button.
Requirement
To configure in the BATCH Control Center, enable the "Force comment when signing" check
box in the "Electronic signatures" tab of the "Project settings" dialog in the Options > Settings
menu.
Signing and comment entry
If an electronic signature with forced comment is configured for an action, the batch remains
at the step at which the signature is required, and a WinCC process control message is
generated. An icon indicating a signature request is displayed at the step and an icon indicating
an operator prompt is displayed at the batch.
Icon
Description
Signature request at the recipe step.
Operator prompt on the batch in the BCC
BATCH Control Center
9.7 Electronic signature
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
379
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...