SIMATIC BATCH engineering
Below, you will find a list of configuration steps that are required for BATCH engineering:
1. Start the BATCH configuration dialog in the SIMATIC Manager using the SIMATIC BATCH
> Open configuration dialog command.
2. In the BATCH configuration dialog, select the highest folder in the navigation area and click
"Settings" in the shortcut menu. Check the settings in all the tabs are set the system
characteristics. Select the OS to which Batch message texts are transferred.
3. If you want to use the "AS-based" mode, you will need to go to the "Stations" folder and
enter or select the percentage of total memory you are using for the allocation of recipe
logic.
4. Update the stations. The necessary S7 connection in the BATCH application is generated
and assigned parameters automatically.
5. Edit the assignment of control strategies.
6. Edit the assignment of parameter groups.
7. Generate the batch types. In a multiproject, you can propagate the batch types to the
projects.
8. Compile the batch instances or merge the batch instances in a multiproject.
9. Assign WinCC archive tags to the configured measured values.
10.Select the folder of your batch process cell in the navigation window. Transfer the messages
to the assigned PCS 7 OS.
11.Download your batch process cell to the database on the SIMATIC BATCH server.
If your configurations have repercussions for the PCS 7 basic data or the BATCH process
cell data, you will be informed of this in the "Loading the process cell data is not possible"
dialog. Configurations that still need to be performed can be started immediately from this
dialog. You can then download the batch process cell.
WARNING
Change to reserved areas in the S7 program
If you change the "Areas reserved for other applications ..." in a S7 program (under Open
CFC chart and then select "Options >Settings >Compile/Download" and make changes),
new block numbers are assigned to the DBs and FCs in the current S7 program. As a
result the DB and/or FC information saved internally for SIMATIC BATCH has to be
updated.
Following a change to the reserved areas you will need to run the SIMATIC BATCH
engineering again.
Additional information
Memory configuration of the CPU being used (Page 198)
Engineering
7.3 BATCH engineering
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA
189
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...