6.2
Process cell configuration
Configuration of the batch process cell takes place along with the basic engineering of the
S7-400 on the Engineering Station (ES) of SIMATIC PCS 7 in SIMATIC Manager (for example
phase and operation types, equipment properties, user data types, units of measure, etc.).
The Batch process cell data are compiled on the Engineering Station and are transferred to
the database (project directory) of SIMATIC BATCH using the "Download target system"
function.
Using the "Read in process cell" or "Update process cell" function in BatchCC, the process
cell data of BatchCC are read in to the BATCH clients.
6.3
Permission management
SIMATIC BATCH uses the central user management of PCS 7.
You define user roles for SIMATIC BATCH (for example operator) and their assignment to the
defined Windows user groups using the SIMATIC Logon software. Within SIMATIC BATCH
(BatchCC), you can restrict the user permissions of a user role even further - for a specific
computer and for a specific unit.
6.4
Recipe creation
Reading in the batch process cell data (Batch engineering data) on any BATCH client with
BatchCC allows the creation of offline data. You create the materials, formula categories and
formulas with the Batch Control Center. You create libraries and master recipes with the Recipe
Editor. Releasing master recipes, library elements and formulas allows their use in process
mode.
6.5
Process mode
The first phase of process mode is batch planning. Here, a production order is created first.
This is divided into individual batch orders (at least one) that are then released and started.
The actual Batch processing programs (equipment phases) run on the programmable
controller and are coordinated by the batch control (BATCH Control Server). Communication
with the equipment phases is done through the WinCC data manager.
The batch data management (Batch CDV) also makes use of individual WinCC components.
From the measured value archive, the values for the required measured value sequences are
obtained for the batch report and all batch-relevant messages are filtered out of the message
archive.
A further important process function is the operator control and monitoring of a batch or the
control recipe. This takes place partly in SIMATIC BATCH itself and partly using Batch
faceplates in WinCC (OS).
Introduction to SIMATIC BATCH
6.5 Process mode
SIMATIC BATCH V8.2
120
Operating Manual, 02/2016, A5E35958174-AA
Содержание SIMATIC BATCH
Страница 30: ...Security information SIMATIC BATCH V8 2 30 Operating Manual 02 2016 A5E35958174 AA ...
Страница 135: ...Example Engineering 7 1 Basic engineering for PCS 7 SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 135 ...
Страница 403: ...BATCH Control Center 9 8 Batch control SIMATIC BATCH V8 2 Operating Manual 02 2016 A5E35958174 AA 403 ...
Страница 584: ...BATCH Recipe Editor 10 5 Other functions SIMATIC BATCH V8 2 584 Operating Manual 02 2016 A5E35958174 AA ...
Страница 722: ...Appendix 13 4 Command line parameters for BatchCC SIMATIC BATCH V8 2 722 Operating Manual 02 2016 A5E35958174 AA ...
Страница 1158: ...Index SIMATIC BATCH V8 2 1158 Operating Manual 02 2016 A5E35958174 AA ...