Maintenance and servicing
6
● Select maintenance cycles so that problems can be recognized in good time. Check the
following:
– The device for visible damage
– That the permitted temperatures are not exceeded
– That the cables are securely connected,
– Damage to cable and wiring entries
– Enclosure gaskets for cracks and damage
– Bonding of seal on the enclosure cover and at the bonding positions
– Surface of seal for damage
● If the seal is damaged, replace the complete cover if necessary.
● If there is damage to the enclosure, there is a risk that the degree of protection is no longer
valid. In some cases, this might necessitate replacement of the enclosure.
● If there is damage to cable and wiring entries, only replacement with original parts is
permitted.
● Check regularly, once a year, that the cable and line entries are securely in place and
properly sealed. Check the tightening torques.
If necessary, re-tighten the glands to the torques specified by the manufacturer. For
information on the torques, refer to the respective manufacturer documentation.
Distributed I/O device 6DL2804-1xxxx & 6DL2804-2xxxx
Hardware Installation Manual, 07/2017, A5E42025214-AA