5.5.5 Technical
data
Insulation group
A according to VDE 0110 § 13 Group 2 for 24 V DC,
15 V DC, 5 V DC
Ambient temperature
0 to +55 degrees C and fan operation (force ventil.)
Storage temperature
-25 to +70 degrees C
Humidity rating
F according to DIN 40050
Altitude rating
S according to DIN 40040
Mechanical rating
Installed in stationary equipment, which is not
necessarily vibration-free
Packaging system
ES 902 C
Dimensions
233.4 mm * 220 mm
Module width
20.14 mm
Installation size
1 slot
Weight 600
g
Rated voltage
min. max.
Typ. current drain
+5 V
+4.75 V
+5.25 V 100 mA
+15 V
+14.4 V
+15.6 V 490 mA (+ encoder load)
-15 V
-15.6 V
-14.4 V 75 mA
24 V (external)
+15V
+30 V
70 mA (+ load of the binary outputs)
No. 2
Version
Output with associated ground,
non-floating
Output voltage range
-10 V to +10 V
Output current
+/- 10 mA
Resolution 12
bits
Monotony
10 bits over the complete temperature range
Absolute accuracy
Typ. 9 bits over the complete temperature range
Short-circuit protection to
ground
Yes
No. 4
non-floating
Input voltage
24 V DC rated voltage
For 0 signal
-1 V to +6 V or inputs open-circuit
For 1 signal
+13 V to +33 V
Input current
For 0 signal
0 mA
For 1 signal
3 mA typ.
Delay time
120 µs
General data
Power supply
Analog outputs,
connector X5
Binary inputs
connector X6
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China